AM-7
Annunciator Module
the panel. Re-install the locking side panels and tighten the Allen screws to secure the enclosure
to the panel. See Figure 2 below.
Rear of
Module
locking
side
panel
Panel
Allen
screw
Figure 2: Rear view of mounted annunciator module
Labeling
The Annunciator Module comes with a blank label on the front on which you can write a de-
scription to identify each light—such as the corresponding alarm or output. We include addi-
tional blank labels for your convenience.
POWER SUPPLY AND GROUNDING
The Annunciator Module operates on 10-15VDC. Typically the module is powered from the
AUX PWR terminals on the SCADA 3000 main unit. This is preferred because the AUX PWR
from the main unit is battery-backed in the event of a power failure, when a battery is connected
to the main unit. Alternately, you may connect the module to any 10-15VDC power source.
The module requires 1.5 Watts of power. See Figure 3.
ABYZ
EG
12VIN
+
RS232-DTE
COM 2
RS232-DCE
COM 1
15V
+IN-
AUX
+PWR-
EG
BAT
+ -
24V
FUSE
SPARE
4A
4
Annunciator Module
SCADA 3000
Connect to Electrical
Earth Ground
AUX
Figure 3: Annunciator Module connected to the SCADA 3000
It is extremely important that the EG pin be connected to a good earth ground. This will
prevent communication errors due to differences in ground potential between modules in
addition to possible damage due to voltage transients and surges.
Komentarze do niniejszej Instrukcji